More than sensors+automation
Search
JUMO GmbH & Co. KG

Moritz-Juchheim-Str 1
36039 Fulda, Germany

Phone: +49 661 6003-0
Fax: +49 661 6003-500
E-mail: mail(at)jumo(dot)net

JUMO mTRON T - Multichannel Controller Module (705010)

Features

  • Up to four PID controller channels each with two parameter sets and four setpoint values
  • Self-optimization using the oscillation or step response method
  • Independent operation
  • Two high-quality, universal analog inputs for thermocouples, RTD temperature probes, resistance transmitters, resistance/potentiometers, or standard signals 
  • Customer-specific linearization (polynomial up to the 4th order)
  • Two digital inputs DC 0/24 V
  • Two digital outputs as a relay with N/O contact or a logic output
  • The inputs and outputs can be extended (option)
  • All analog inputs are electrically isolated from each other
  • Limit value monitoring
  • One counting input up to 10 kHz
  • Automatic configuration after the module insert has been exchanged
  • Connection of the inputs and outputs at the front
  • Removable terminal strips with Push-In technology
  • Quick wiring of operating voltage and system bus due to easy module connection

System Technology JUMO mTRON T

Description

The multichannel controller module supports up to four PID ontroller channels (cascadable). In the standard version, two high-quality universal analog inputs for thermocouples, RTD temperature probes, resistance transmitters, resistance/potentiometers, and standard signals are available. Two digital inputs (DC 0/24 V) and two digital outputs as a relay with N/O contact (AC 230 V / 3 A) or as a logic output (DC 0/15 V) are also available as part of the standard version. Due to the three option slots (option 1, 2, and 3), the module can be extended up to four universal analog inputs, eight digital inputs, three analog outputs, or eight digital outputs.

The digitized input values/states are available in the system for further processing. The digital and the analog outputs can be actuated by the system (via the connection list or directly by the PLC) or directly by the module.

The module operates independently, even if the central processing unit fails or the higher-ranking system malfunctions. This behavior can be configured.

LEDs are used to indicate applied voltage supply, the module operating status, and the status of the digital inputs/outputs.

For expansion of the inputs/outputs or for service work, the module insert can be easily pulled out of the case at the front. The case including the bus PCB remains mounted on the DIN rail.

A setup program can be used to comfortably configure and parameterize the multichannel controller module.

Article number Product description Price / piece