More than sensors+automation
Search

Input 1: Hardware alteration between universal input and 0 - 10 V.

On a standard universal input (resistance thermometer, thermocouple, current) the solder links S101 and S102 on the CPU board are assigned as follows:

* solder link S101 a and b linked, a and c open
* solder link S102 open

If input 1 has to operate off 0 - 10 V (other signals are then no longer possible!), the solder links on the CPU board must be changed as follows:

* solder link S101 a and c linked, and a and b open.
* solder link S102 closed


Assignment of links for input signal 0 - 10V for input 1:

P2_3_Q6_DE