What is to be taken into account for setting a limit value controller?

In configuration level C211- Controller options, set limit value controller for K1 and K2.
C211- 11xx
In configuration level C212 – Controller outputs, ensure that MIN/MAX and NOC/NCC is set.
C212 – xx10
In configuration level C213 – Other outputs I, the alarm monitoring of relays K1 and K2 is activated for the set point values respectively set.
C213 xxx0
In configuration level C214 – Other outputs II, activate the function (limit value controller) set in configuration level C211-11xx.
C214 – xx11
Note: For this, also refer to chapter 14 Configuration level in the operating instructions Type 202530.